Applicable Tools; Operating Procedure - YASKAWA SGD7S series Product Manual

Sigma-7-series ac servo drive. sigma-7s servopack with analog voltage/pulse train references
Hide thumbs Also See for SGD7S series:
Table of Contents

Advertisement

6.15.2

Applicable Tools

The following table lists the tools that you can use to initialize the vibration detection level and
the applicable tool functions.
Tool
Panel Operator
Digital Operator
SigmaWin+
6.15.3

Operating Procedure

Use the following procedure to initialize the vibration detection level.
1.
Click the
2.
Select Initialize Vibration Detection Level in the Menu Dialog Box.
The Initialize Vibration Detection Level Dialog Box will be displayed.
3.
Select Pn311: Vibration Detection Sensitivity and Pn310: Vibration Detection Selec-
tions and then click the Detection Start Button.
A setting execution standby mode will be entered.
Function
Fn01B
Fn01B
Setup
Initialize Vibra-
tion Detection Level
Servo Drive Button in the workspace of the Main Window of the SigmaWin+.
6.15 Initializing the Vibration Detection Level
Operating Procedure Reference
13.4.20 Initialize Vibration Detection Level (Fn01B) on
page 13-27
Σ-7-Series Digital Operator Operating Manual (Manual
No.: SIEP S800001 33)
6.15.3 Operating Procedure on page 6-99