7.4 Trial Operation from the Host Controller for the Servomotor without a Load
7.4.1 Preparing the Servomotor for Trial Operation
Make sure that a reference is not being input.
If you are using a safety function, make sure that the safety function device is con-
nected to CN8.
Refer to the following section for the safety function device connection method.
3.
Connect the I/O Signal Cable to the I/O signal connector (CN1).
4.
Turn ON the power supplies to the SERVOPACK.
The control power and main circuit power will be supplied.
5.
Confirm that the Panel Operator display is as shown below.
6.
If you are using an absolute encoder, turn ON the SEN signal.
The current position will be read from the absolute encoder.
This step is not necessary if you are using an incremental encoder.
7.
Check the status of the I/O signals.
• Using the SigmaWin+: Monitor - Wiring Check
• Using the Panel Operator or Digital Operator: Un005 (Input Signal Monitor)
The correct states of the input signals are given in the following table. If the actual states do not agree
with those given in the following table, correct the I/O signals.
/S-ON (Servo ON) Signal
/P-CON (Proportional Control) Signal
P-OT (Forward Drive Prohibit) Signal
N-OT (Reverse Drive Prohibit) Signal
/ALM-RST (Alarm Reset) Signal
/P-CL (Forward External Torque Limit) Signal
/N-CL (Reverse External Torque Limit) Signal
SEN (Absolute Data Request) Signal
8.
Input the /S-ON (Servo ON) signal.
The servo will turn ON.
7-12
4.6 Connecting Safety Function Signals
You can set Pn002 to n.1 (Use the encoder as an incremental encoder) to tem-
Information
porarily use an absolute encoder as an incremental encoder. This makes it possible to
perform trial operation without setting up the absolute encoder or setting the SEN sig-
nal.
CN1
Signal
on page 4-48
Correct State
OFF
OFF
ON
ON
OFF
OFF
OFF
• When using an absolute encoder: ON
• When not using an absolute encoder: OFF