Remove a Power Supply

-> show /SYS/PSx/V_12V value
/SYS/PS0/V_12V
Properties:
value = 12.027 Volts
->
where x is 0 (lower power supply) or 1 (upper power supply).
If the power supply is faulty, replace it. See
8.
If you are unable to determine if a power supply is faulty, seek further
information.
See
"Detecting and Managing Faults" on page
Related Information
"Remove a Power Supply" on page 122
"Power Supply LEDs" on page 120
"Verify a Power Supply" on page 126
"Detecting and Managing Faults" on page 21
Remove a Power Supply
Removing a power supply is a hot-swap operation. You do not need to power off the server
before you remove the power supply.
1.
Determine which power supply to remove.
See
"Locate a Faulty Power Supply" on page
Consider your next step.
2.
If you have not prepared for service, do so now. See
If you are removing a power supply as part of another component's removal or installation
procedure, go to
3.
Disconnect the power cord from the power supply.
See
"Disconnect Power Cords and Data Cables" on page
122
Netra Server X5-2 Service Manual • October 2016
"Remove a Power Supply" on page
Step
3.
21.
120.
"Preparing for Service" on page
70.
122.
61.