Oracle netra X5-2 Service Manual page 121

Hide thumbs Also See for netra X5-2:
Table of Contents

Advertisement

health_details = -
...
->
If the health_details property identifies a faulty power supply, replace it. See
Power Supply" on page
4.
Check the health of the individual power supplies.
-> show /System/Power/Power_Supplies/Power_Supply_x
/System/Power/Power_Supplies/Power_Supply_0
Targets:
Properties:
health = OK
health_details = -
...
->
where x is the number of the power supply, either 0 (lower power supply) or 1 (upper power
supply).
If the health_details property identifies the power supply as faulty, replace it. See
Power Supply" on page
5.
Verify that a power supply is faulty.
If a power supply is faulty, you will see /SYS/PSx under the Value heading, where x is 0 (lower
power supply) or 1 (upper power supply).
For example:
-> show faulty
Target
--------------------+------------------------+-------------------------------
/SP/faultmgmt/0
...
->
If a power supply is faulty, replace it. See
If a FRU value different from /SYS/PSx is displayed, see
Reference" on page 65
6.
Use the Oracle ILOM faultmgmt shell to identify the faulty component.
See
"Display Faults (faultmgmt Shell)" on page
Check the Fault class and Description fields for more information.
If a power supply is faulty, replace it. See
7.
Within the Oracle ILOM interface, verify the voltage output.
122.
122.
| Property
| fru
"Remove a Power Supply" on page
to identify which component is faulty.
"Remove a Power Supply" on page
Locate a Faulty Power Supply
| Value
| /SYS/PS0
"Component Service Task
48.
Servicing Power Supplies
"Remove a
"Remove a
122.
122.
121