Electrical installation
4.11 Other connections
4.11.22

SMC30 Sensor Module Cabinet-Mounted (option K50)

4.11.22.1

Description

The SMC30 Sensor Module is used for determining the actual motor speed. The signals
emitted by the rotary pulse encoder are converted here and made available to the closed-
loop controller via the DRIVE-CLiQ interface for evaluation purposes.
In conjunction with SINAMICS G150 the following sensors can be connected to the SMC30
Sensor Module:
● TTL encoder
● HTL encoder
● KTY or PTC temperature sensor
Table 4- 65
Connectable encoders with supply voltage
Encoder type
HTL bipolar 24 V
HTL unipolar 24 V
TTL bipolar 24 V
TTL bipolar 5 V
TTL unipolar
Table 4- 66
Note
Because the physical transmission media is more robust, the bipolar connection should
always be used for HTL encoders. The unipolar connection should only be used if the
encoder type does not output push-pull signals.
NOTICE
Only one encoder system may be connected to the encoder module, either at X520 or at
X521/X531. The corresponding unused interface must not be used.
166
X520 (SUB-D)
X521 (terminal)
Yes
Yes
Yes
Yes
No
Maximum signal cable lengths
Encoder type
TTL
HTL unipolar
HTL bipolar
X531 (terminal)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
Open-circuit
monitoring
Yes
No
Yes
Yes
No
Maximum signal cable length in m
100
100
300
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A
Remote sense
No
No
No
To X520