Operation
6.7 Communication according to PROFIdrive
Error
value
0x82
Transfer of the control authority is
inhibited by BI: p0806.
0x83
Parameter %s [%s]: requested BICO
interconnection not possible.
0x84
Parameter %s [%s]: parameter
change inhibited
(refer to p0300, p0400, p0922)
0x85
Parameter %s [%s]: access method
not defined.
0xC8
Below currently valid limit.
0xC9
Above currently valid limit.
0xCC
Write access not permitted.
328
Meaning
Comment
BICO output does not supply float values, however the
BICO input requires float values.
Modification request for a value that, although within
"absolute" limits, is below the currently valid lower limit.
Modification request for a value that, although within
"absolute" limits, is above the currently valid upper limit
(e.g., specified by the actual converter rating).
Write access is not permitted because an access code is
not available.
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A
Additional
info