Electrical installation
4.11 Other connections
Diagnostics
For a description of messages output during operation and in the event of faults (meaning of
LEDs on -B101), consult the Operating Instructions in the customer DVD supplied with the
device.
4.11.19
CBC10 CAN Communication Board (option G20)
Description
Figure 4-28
The CBC10 CANopen communication board (CAN Communication Board) is used to
connect drives in the SINAMICS drive system to higher-level automation systems with a
CAN bus.
The CANopen Option Board uses two 9-pin SUB D connectors for the connection to the
CAN bus system.
The connectors can be used as inputs or outputs. Unused pins are plated through.
Among others, the following transmission rates are supported: 10, 20, 50, 125, 250, 500, 800
kBaud, and 1 Mbaud.
CAUTION
The Option Board may only be inserted and removed when the Control Unit and Option
Board are disconnected from the power supply.
The CBC10 must only be operated by qualified personnel. The ESD notices must be
observed.
The module is inserted in the option slot of the Control Unit at the factory.
154
CAN CBC10 Communication Board
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A