Siemens SINAMICS G150 Operating Instructions Manual page 517

Converter cabinet units 75 kw to 1500 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

LED
Color
DP
---
PROFIdrive cyclic
operation
Green
Red
OPT
---
(OPTION)
Green
Red
RDY and DP
Red
RDY and OPT
Orange
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A
State
Description
OFF
Cyclic communication is not (yet) running.
Note:
PROFIdrive is ready for communication when the control unit is
ready for operation (see RDY LED).
Continuous light
Cyclic communication is taking place.
0.5 Hz flashing
Cyclic communication has still not been fully established.
light
Possible causes:
- The controller is not transmitting any setpoints.
- In isochronous mode, the controller did not send a Global Control
or it sent a defective Global Control (GC).
0.5 Hz flashing
PROFIBUS master is sending incorrect parameter
light
assignment/configuration
2 Hz flashing light
Cyclic bus communication has been interrupted or could not be
established.
OFF
Electronic power supply outside permissible tolerance range.
The component is not ready for operation.
The Option Board is missing or an associated drive object has not
been created.
Continuous light
Option Board is ready.
0.5 Hz flashing
Depends on the Option Board used.
light
2 Hz flashing light
This component has at least one fault.
The option board is not ready (e.g., after switching on).
2 Hz flashing light
Bus error - communication has been interrupted.
0.5 Hz flashing
Firmware update in progress for connected option board CBE20.
light
Diagnosis / faults and alarms
10.2 Diagnosis
515