Setpoint channel and closed-loop control
7.3 V/f control
Table 7- 1
p1300 V/f characteristics
Parameter
Meaning
value
0
Linear characteristic
1
Linear characteristic
with flux current
control (FCC)
2
Parabolic
characteristic
3
Programmable
characteristic
4
Linear characteristic
and ECO
376
Standard with variable voltage boost
Characteristic that compensates for voltage
losses in the stator resistance for static /
dynamic loads (flux current control FCC).
This is particularly useful for small motors,
since they have a relatively high stator
resistance.
Characteristic that takes into account the
motor torque curve (e.g. fan/pump).
Quadratic characteristic (f² characteristic)
Energy saving because the low voltage
also results in small currents and losses.
Characteristic that takes into account the
motor/machine torque characteristic.
Characteristic (see parameter value 0) and Eco mode at constant operating point.
At constant operating point, the efficiency is optimized by varying the voltage.
Active slip compensation is necessary here; the scaling must be set so that the
slip is fully compensated (p1335 = 100%).
Application / property
V
V
n
0
V
V
n
0
V
V
max
r0071
p1327
p1325
p1323
p1321
r1315
0
f1
p1320
Operating Instructions, 03/2012, A5E03263466A
f
f
n
f
f
n
f
f 4
f max
f2
f3
p1082
p1322
p1324
p1326
Converter cabinet units