Diagnosis / faults and alarms
10.2 Diagnosis
Parameter
Name
Description
If r0035 does not equal -200.0 °C, the following applies:
This temperature indicator is valid.
An KTY sensor is connected.
If using an asynchronous motor, the thermal motor model is activated (p0600 = 0 or p0601 = 0).
If r0035 equals -200.0 °C, the following applies:
This temperature indicator is invalid (temperature sensor fault).
An PTC sensor is connected.
If using a synchronous motor, the thermal motor model is activated (p0600 = 0 or p0601 = 0).
r0037
CO: Power unit temperatures
Displays the measured temperatures in the Power Module.
r0046
CO/BO: Missing enable signals
Displays missing enable signals that are preventing the closed-loop drive control from being commissioned.
r0049
Motor data set/encoder data set active (MDS, EDS)
Displays the effective motor data set (MDS) and the effective encoder data sets (EDS).
r0050
CO/BO: Command Data Set CDS effective
Displays the effective command data set (CDS)
r0051
CO/BO: Drive Data Set DDS effective
Effective drive data set (DDS) display.
r0056
CO/BO: Status word, closed-loop control
Displays the status word of the closed-loop control.
r0063
CO: Speed actual value
Displays the actual speed for speed control and U/f control.
r0066
CO: Output frequency
Displays the output frequency of the Motor Module.
r0070
CO: Actual DC link voltage
Displays the measured actual value of the DC link voltage.
r0072
CO: Output voltage
Displays the actual output voltage of the power unit (Motor Module).
r0082
CO: Active power actual value
Displays the instantaneous active power.
r0206
Rated power module power
Displays the rated power module power for various load duty cycles.
r0207
Rated power module current
Displays the rated power module power for various load duty cycles.
r0208
Rated power module line supply voltage
Displays the rated line supply voltage of the power unit.
r0209
Power unit, maximum current
Displays the maximum output current of the power unit.