Siemens SINAMICS G150 Operating Instructions Manual page 114

Converter cabinet units 75 kw to 1500 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Electrical installation
4.10 Signal connections
S5: Selector for voltage/current AI0, AI1
Table 4- 25
Selector for voltage/current S5
S5.0
S5.1
Note
When delivered, both switches are set to current measurement (switch set to "I").
X522: 2 analog outputs, temperature sensor connection
Table 4- 26
Terminal block X522
Terminal
1
2
3
4
5
6
7
8
AO xV: analog output voltage; AO xC: Analog output current
1)
Max. connectable cross-section: 1.5 mm²
Risk of electric shock!
Only temperature sensors that meet the safety isolation specifications stipulated in
EN 61800-5-1 may be connected to terminals "+Temp" and "-Temp".
If these instructions are not complied with, there is a risk of electric shock!
Note
The following sensors can be connected to the temperature sensor connection:
• KTY84-1C130
• PTC
112
Switch
Selector voltage (V) / current (I) Al0
Selector voltage (V) / current (I) Al1
Designation
1)
AO 0V+
-10 ... +10 V (max. 3 mA)
+4 ... +20 mA (max. load resistance ≤ 500 Ω)
AO 0-
-20 ... +20 mA (max. load resistance ≤ 500 Ω)
AO 0C+
0 ... +20 mA (max. load resistance ≤ 500 Ω)
AO 1V+
Resolution: 11 bits + sign
AO 1-
continued short-circuit proof
AO 1C+
+Temp
Temperature sensor connection:
- KTY84-1C130
-Temp
- PTC
DANGER
Function
Technical data
Operating Instructions, 03/2012, A5E03263466A