Example 2: connection of OC/OFF3 to several drives
The OFF3 signal is to be connected to two drives via terminal DI 2 on the Control Unit.
Each drive has a binector input 1. OFF3 and 2. OFF3. The two signals are processed via an
AND gate to STW1.2 (OFF3).
Figure 6-8
BICO interconnections to other drives
The following parameters are available for BICO interconnections to other drives:
• r9490
• r9491[0...15]
• r9492[0...15]
• p9493[0...15]
Binector-connector converters and connector-binector converters
Binector-connector converter
● Several digital signals are converted to a 32-bit integer double word or to a 16-bit integer
● p2080[0...15] BI: PROFIdrive PZD send bit-serial
Connector-binector converter
● A 32-bit integer double word or a 16-bit integer word is converted to individual digital
● p2099[0...1] CI PROFIdrive PZD selection receive bit-serial
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A
Connection of OFF3 to several drives (example)
Number of BICO interconnections to other drives
BI/CI of BICO interconnections to other drives
BO/CO of BICO interconnections to other drives
Reset BICO interconnections to other drives
word.
signals.
6.3 Basic information about the drive system
Operation
273