Safe Brake Adapter Sba 24 V Dc (Option K89) - Siemens SINAMICS G150 Operating Instructions Manual

Converter cabinet units 75 kw to 1500 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

4.11.29

Safe Brake Adapter SBA 24 V DC (option K89)

Description
Safe Brake Control (SBC) is a safety function that is used in safety-related applications. In
the no-current state, the brake acts on the motor of the drive using spring force. The brake is
released (opened) when current flows through it (=low active).
The Safe Brake Adapter 24 V DC is installed in the cabinet unit in the factory. An infeed is
connected to terminal -X13 on the Safe Brake Adapter to provide the necessary power. For
control, a connection is established between the Safe Brake Adapter and the Control
Interface Module using a cable harness installed in the factory.
For controlling the brake, on the plant side, a connection must be established between
terminal -X14 on the Safe Brake Adapter and the brake.
Maximum cable length of the brake control
The maximum permissible cable length of 30 m between the Safe Brake Adapter 24 V DC
and the brake must be observed. To accurately calculate the maximum cable length, see
the SINAMICS Low Voltage Engineering Manual on the customer DVD supplied with the
device.
Notes
Note
Replacement fuses
The order numbers for spare fuses can be taken from the spare parts list supplied.
Note
The integrated safety functions, starting from the Safety Integrated (SI) input terminals of the
SINAMICS components (Control Unit, Motor Module), satisfy the requirements according to
EN 61800-5-2, EN 60204-1, DIN EN ISO 13849-1 Category 3 (formerly EN 954-1) for
Performance Level (PL) d and IEC 61508 SIL2.
With the Safe Brake Adapter (option K89), the requirements specified in EN 61800-5-2, EN
60204-1, DIN EN ISO 13849-1 Category 3 (formerly EN954-1) as well as for Performance
Level (PL) d and IEC 61508 SIL 2 are fulfilled.
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A
WARNING
Electrical installation
4.11 Other connections
183

Advertisement