Operation
6.6 Control via the operator panel
Normalization for VECTOR object
Table 6- 8
Normalization for VECTOR object
Size
Reference speed
Reference voltage
Reference current
Reference torque
Reference power
Reference frequency
Reference modulation
depth
Reference flux
Reference temperature
TM31 object
Table 6- 9
List of signals for the operation screen – TM31 object
Signal
Analog input 0 [V, mA]
Analog input 1 [V, mA]
Analog input 0, scaled
Analog input 1, scaled
Setting the date/time (for date stamping of error messages)
In this menu, you set the date and time.
You can also set whether and/or how the AOP and drive unit are to be synchronized.
Synchronization of the AOP with the drive enables error messages to be date- and time-
stamped.
Note
The drive unit displays the time in parameter r3102 in the UTC format (days/milliseconds
since 01/01/1970 ).
298
Scaling parameter
100% = p2000
100% = p2001
100% = p2002
100% = p2003
100% = r2004
100% = p2000/60
100 % = Maximum output voltage without overload
100 % = Rated motor flux
100% = 100°C
Parameter
r4052[0]
r4052[1]
r4055[0]
r4055[1]
Default for quick commissioning
p2000 = Maximum speed (p1082)
p2001 = 1000 V
p2002 = Current limit (p0640)
p2003 = 2 x rated motor torque
r2004 = (p2003 x p2000 x π) / 30
Short name
Unit
AI_UI
V, mA
AI_UI
V, mA
AI_%
%
AI_%
%
Operating Instructions, 03/2012, A5E03263466A
Scaling
(100 % = ...)
V: 100 V / mA: 100 mA
V: 100 V / mA: 100 mA
as set in p200x
as set in p200x
Converter cabinet units