Maintenance and servicing

11.2 Maintenance

During connection, installation and repair work on units that are connected in parallel, it
must be ensured that both sub-cabinets are electrically disconnected from the power
supply.
11.2
Maintenance
The cabinet unit mainly comprises electronic components. Apart from the fan(s), the unit
contains very few components that are subject to wear or require maintenance or servicing.
Maintenance aims to preserve the specified condition of the cabinet unit. Dirt and
contamination must be removed regularly and parts subject to wear replaced.
The following points must generally be observed.
11.2.1

Cleaning

Dust deposits
Dust deposits inside the cabinet unit must be removed at regular intervals (or at least once a
year) by qualified personnel in line with the relevant safety regulations. The unit must be
cleaned using a brush and vacuum cleaner, and dry compressed air (max. 1 bar) for areas
that cannot be easily reached.
Ventilation
The ventilation openings in the cabinet must never be obstructed. The fan must be checked
to make sure that it is functioning correctly.
Cable and screw terminals
Cable and screw terminals must be checked regularly to ensure that they are secure in
position, and if necessary, retightened. Cabling must be checked for defects. Defective parts
must be replaced immediately.
Note
The actual intervals at which maintenance procedures are to be performed depend on the
installation conditions (cabinet environment) and the operating conditions.
Siemens offers its customers support in the form of a service contract. For further details,
contact your regional office or sales office.