Siemens SINAMICS G150 Operating Instructions Manual page 87

Converter cabinet units 75 kw to 1500 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

CAUTION
If the terminals are not reconnected to the actual line voltage:
• The required cooling capacity cannot be provided because the fan rotates too slowly.
• The fan fuses may blow due to an overcurrent.
Note
The order numbers for fan fuses that have blown can be found in the spare parts list.
Table 4- 6
Table 4- 7
Table 4- 8
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A
Line voltage assignment for the setting at the fan transformer
(380 ... 480 V 3 AC)
Line voltage
380 V ± 10%
400 V ± 10%
440 V ± 10%
480 V ± 10%
Line voltage assignment for the setting at the fan transformer
(500 ... 600 V 3 AC)
Line voltage
500 V ± 10%
525 V ± 10%
575 V ± 10%
600 V ± 10%
Line voltage assignment for the setting at the fan transformer
(660 ... 690 V 3 AC)
Line voltage
660 V ± 10%
690 V ± 10%
Taps of the fan transformer (-T1- T10)
380 V
400 V
440 V
480 V
Taps of the fan transformer (-T1- T10)
500 V
525 V
575 V
600 V
Taps of the fan transformer (-T1- T10)
660 V
690 V
Electrical installation
4.8 Power connections
85