Siemens SINAMICS G110M Getting Started

Distributed converter for simogear geared motors
Hide thumbs Also See for SINAMICS G110M:

Advertisement

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SINAMICS G110M

  • Page 3 ___________________ SINAMICS G110M Getting Started Safety instructions ___________________ Description ___________________ SINAMICS Installation ___________________ Commissioning SINAMICS G110M SINAMICS G110M Getting Started ___________________ Troubleshooting Getting Started Edition 09/2014, Firmware V4.7 09/2014, FW V4.7 A5E31298643B AC...
  • Page 4 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 5: Table Of Contents

    Residual risks of power drive systems ..................12 Description ............................15 Identifying the components of the system ................15 SINAMICS G110M converter ....................16 General layout SINAMICS G110M system ................23 Installation ............................27 Mechanical Installation......................28 3.1.1 Dimensions of converters and motors ..................28 System Installation ........................
  • Page 6 4.8.4 Identifying motor data ......................84 4.8.5 Change settings ........................85 4.8.6 Optimize the drive using the trace function ................87 Troubleshooting ............................ 91 Status LED overview ......................91 SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 7: Safety Instructions

    • Only use power supplies that provide SELV (Safety Extra Low Voltage) or PELV- (Protective Extra Low Voltage) output voltages for all connections and terminals of the electronics modules. SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 8 • Additionally, select the installation site so that an uncontrolled spreading of smoke can be avoided in the case of a fire. • Ensure that smoke can escape via designated paths. SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 9 All converters and motors are subject to a high voltage test in the manufacturer's facility. As a consequence, it is not necessary to carry out additional tasks in the system/machine. SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 10: Safety Instructions For Electromagnetic Fields (Emf)

    • If affected by this, keep a distance of at least 2 m. Handling electrostatic sensitive devices (ESD) Electrostatic sensitive devices (ESD) are individual components, integrated circuits, modules or devices that may be damaged by either electric fields or electrostatic discharge. SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 11: Industrial Security

    Note Industrial security Siemens provides automation and drive products with industrial security functions that support the secure operation of plants or machines. They are an important component in a holistic industrial security concept. With this in mind, our products undergo continuous development.
  • Page 12: Residual Risks Of Power Drive Systems

    These components may only be handled by qualified and trained technical personnel who are knowledgeable and observe all of the safety instructions on the components and in the associated technical user documentation. SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 13 5. Release of environmental pollutants or emissions as a result of improper operation of the system and/or failure to dispose of components safely and correctly. SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 14 For more information about residual risks of the components in a drive system, see the relevant sections in the technical user documentation. SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 15: Description

    Description Identifying the components of the system The SINAMICS G110M is a complete converter system for controlling the speed of a three- phase motor. Each part of the system is shown in the following figure. Figure 2-1 Identifying the components of the system SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 16: Sinamics G110M Converter

    Description 2.2 SINAMICS G110M converter SINAMICS G110M converter Overview The SINAMICS G110M system consists of the following components: ● Terminal Housing (including the Control Module) ● Power Module ● Three-phase motor. The Power Modules are designed for a specific power range and the terminal housings are designed to work with specific motors.
  • Page 17 FS100/112 HanQ 4/2 / 7/8" 6SL3544-0QB02-1FA0 Every SINAMICS G110M is delivered with the following accessories: All variants ● PTC connection cable - this is the extension cable used to connect the PTC wires from the motor to the connection on the CPI board.
  • Page 18 The following tables detail the motors that are compatible with the SINAMICS G110M system. Due to the unique nature of the SINAMICS G110M system, there are a number of restrictions regarding the type of options and devices used with the motors. These are listed below: ●...
  • Page 19 Rules for the use of the motors: ● Rated output current of the converter ≥ rated input current of the motor. ● For the SINAMICS G110M use only the following types of motors: – SIMOTICS GP 1LA, frame size 71 –...
  • Page 20 Description 2.2 SINAMICS G110M converter SINAMICS G110M characteristics Motor characteristics HO power Rated output Frame size Order num- Power (kW) Frame size Rated current Efficiency (kW) current (A) 4.10 1LA7070- 0.37 0.99 1LA9070- 0.37 0.95 1LE1001- 0.75 1.67 0DA2 1LE1001- 1.10...
  • Page 21 Description 2.2 SINAMICS G110M converter SINAMICS G110M characteristics Motor characteristics HO power Rated output Frame size Order num- Power (kW) Frame size Rated current Efficiency (kW) current (A) 1LE1001- 2.20 4.50 0EA4 1LE1001- 3.00 100L 6.10 1AA4 1LE1001- 112M 7.80...
  • Page 22 Description 2.3 General layout SINAMICS G110M system SINAMICS G110M characteristics Motor characteristics HO power Rated output Frame size Order num- Power (kW) Frame size Rated current Efficiency (kW) current (A) 1LE1001- 0.75 1.79 0DB3 1LE1001- 1.10 2.50 0EB0 1LE1001- 1.50 3.30...
  • Page 23: General Layout Sinamics G110M System

    Description 2.3 General layout SINAMICS G110M system General layout SINAMICS G110M system Introduction The locations and description of the various interface connections of the CU240M Terminal housing (including the Control Module (CM)) and the PM240M Power Module (PM) are detailed in the figure and table below.
  • Page 24 Description 2.3 General layout SINAMICS G110M system Figure 2-3 General layout of the system SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 25 Description 2.3 General layout SINAMICS G110M system Table 2- 6 Description and location of interfaces Item Description Item Description Power Module Blanking plate - to seal the opposite side of the Terminal Housing from which the CPI has been fitted.
  • Page 26 Description 2.3 General layout SINAMICS G110M system SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 27: Installation

    Should substantial weight be placed on the system it could result in severe damage to the equipment which could adversely affect the application and any persons coming in contact with the system. SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 28: Mechanical Installation

    GREEN and indicated by the ground symbol. These fixing points provide the correct earthing between the terminal housing and the motor and MUST be used. All fixing bolts for the terminal housing are supplied with each terminal housing. SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 29 To ensure that the correct motor is selected the following sources of information should be consulted: ● The relevant system catalog, for example the SINAMICS G120 catalog. ● The relevant motor catalog. ● The Siemens "Configurator" online software application for dimensioning motors (Siemens motor configurator (https://eb.automation.siemens.com/goos/catalog/Pages/ProductData.aspx?catalogRegio n=WW&language=en&nodeid=10028832&tree=CatalogTree&regionUrl=%2F&autoopen= false&activetab=product#topAnch&activetab=config&))
  • Page 30 Figure 3-3 Example of the data available from the Sizer program Mounting orientation The G110M system has been designed to operate in any orientation depending on the motor mounting configuration. SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 31: System Installation

    It is also possible that the SINAMICS G110M system is delivered as separate components, which will require the system to be fitted together before installation and commissioning can take place.
  • Page 32 In some illustrations, components have been removed to enhance the clarity of what is being described. SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 33 3.2 System Installation Note Use only Non-Drive End (NDE) motor configurations The SINAMICS G110M has been designed to be used in conjunction with NDE motors. Do not use standard motor terminal box mountings with the SINAMICS G110M systems. Disassembly procedure When the SINAMICS G110M is delivered as separate components, the terminal housing must be fitted to the motor.
  • Page 34 There are no screws holding down the connectors - they are • secured and held in place when the Control Module is fitted. SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 35 Installation 3.2 System Installation Installation procedure Having dismantled the SINAMICS G110M Terminal Housing, the following procedure should be performed to complete the installation of the whole system. Star and Delta Configuration Configure the motor terminals for either star or delta configuration depending upon the voltage requirement of the application and the mains input voltage.
  • Page 36 For further information, please refer to the following doc- ument: LA/LE motors for mounting on SIMOGEAR gearboxes (http://support.automation.siemens.com/WW/view/en/60666508). If the SINAMICS G110M is ordered as a complete system, then • all mechanical and electrical installation is completed in the facto- ry prior to delivery.
  • Page 37 • If a brake is not used the cable entry must be sealed with a • blanking plug to ensure the IP65 rating of the system is main- tained. SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 38 The final connection of the temperature sensor cannot be com- • pleted until the CPI has been fitted. This will be done after the CPI is fitted, as shown later in this procedure. SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 39 2. Tighten the earthing post screw to 1.5 Nm. Note: If the SINAMICS G110M is ordered as a complete system, then all mechanical and electrical installation is completed in the factory prior to delivery. Connecting the mains cables (HANQ variant) 1.
  • Page 40 3. Connect the L1, L2 and L3 terminals of the terminal housing to the output cable through the cable gland. Note: On the glanded variant no pre-cut cables are provided. SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 41 The internal braking resistor can be fitted on the left or right side of the terminal housing, but must always be fitted on the opposite side of the terminal housing from Communications and Power Interface (CPI). SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 42 • the left or right side of the terminal housing, but must always be fitted on the opposite side of the terminal housing from the inter- nal braking resistor. SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 43 18. PROFIBUS / USS network termination switch When using the PROFIBUS or USS communications protocols, the last converter on the network must have the network termination switch in the ON position. SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 44 20. Fit Power Module onto the terminal housing The Power Module is fitted on top of the terminal housing and screwed in place with the four self-retaining screws. Note: Screws tightening torque: 2.0 Nm. SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 45: Grounding The Terminal Housing

    G110M system. ● Connect the PE terminal on the left-hand side of the inverter to appropriate grounding point of the installation. ● Use a short wire connection. SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 46: Installing The 24V Power Supply

    The optional 24V PSU can be ordered using the following order number: 6SL3555-0PV00-0AA0 A brief description of the layout and the connections of the 24V PSU are given in the following figure. SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 47 ● Since the 24V PSU utilizes the DC link voltage to provide the 24V supply to the Control Module, when the mains supply is disconnected, all power will be lost to the Control Module. SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 48 9. Fit the CM back into place - ensuring that it securely fastened into place. 10.Replace the PM. 11.Fit blanking cap to the 7/8th connector. 12.Power can now be restored to the system. Figure 3-6 Fitting the input and output connections SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 49: Electrical Installation

    Installation 3.3 Electrical Installation Electrical Installation 3.3.1 SINAMICS G110M Electrical data Power Module specifications - 3AC 380 V (-10%) ... 480 V (+10%) Table 3- 2 Rated Output, Input and Fuses Product Frame size Rated output Fuse Rated output Rated input 3NA3…...
  • Page 50 * The optional 24 V PSU is an orderable item which is designed specifically for use with the SINAMICS G110M converter. The 24 V PSU is fitted to the terminal housing as shown in Installing the 24V power supply (Page 46). The external 24 V supply is sourced by the user and is connected to the converter through the 24 V connections as shown in Connection and cables (Page 53).
  • Page 51: Connections And Interference Suppression

    CAUTION Thermal stability of the system The SINAMICS G110M system is comprised of a motor and a converter which are designed to work together. The system can generate a significant amount of heat which can affect the performance of your application.
  • Page 52: Basic Emc Rules

    ● Use only metallic or metallized connector housings for shielded data cables (for example, PROFIBUS cables). SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 53: Connection And Cables

    In some cases, it is possible to extend the cable length by the use of appropriate repeaters. The maximum cable lengths for the various communications protocols are given in the following table: SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 54 500 kbit/s 400 m (1,312 ft) 1.5 Mbit/s 200 m (656 ft) 3, 6 and 12 Mbit/s 100 m (328 ft) PROFINET CAT5 network cable 100 m (328 ft) SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 55 Installation 3.3 Electrical Installation Outline block diagram Figure 3-7 Outline block diagram SINAMICS CU240M and PM240M SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 56 Cable, connectors and tools specifications The detailed specifications for the cables, connectors and tools required to manufacture the necessary cables for the SINAMICS G110M are listed in the following documents and can be accessed using the relevant links: ● SINAMICS and motors for Single-Axis Drives D31 catalog: SINAMICS and motors for Single-Axis Drives D31 catalog (https://intranet.automation.siemens.com/mcms/infocenter/content/en/Pages/order_form.asp...
  • Page 57 Installation 3.3 Electrical Installation Figure 3-8 SINAMICS G110M CU240M USS terminal diagram SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 58 Installation 3.3 Electrical Installation Figure 3-9 SINAMICS G110M CU240M PROFIBUS terminal diagram SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 59 Installation 3.3 Electrical Installation Figure 3-10 SINAMICS G110M CU240M PROFINET terminal diagram When the HAN Q4/2 connector is used on the CPI/terminal housing the mains supply connections are shown in the following figure. SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 60 Further adaption of the inputs and outputs of the Inverter are possible, please refer to relevant section in the SINAMICS G110M Operating Instructions for further information. The internal motor and power connections on the G110M system are located inside the Control Unit and motor housing.
  • Page 61: Cable Protection

    Installation using power-through daisy chain The SINAMICS G110M system has been designed to allow a converter to utilize power- through to provide the mains power for a number of converters in a daisy chain. The maximum current limits for the daisy chain are given below: ●...
  • Page 62 Installation 3.3 Electrical Installation Figure 3-14 Daisy chaining power between Inverters SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 63: Commissioning

    Commissioning Commissioning tools Figure 4-1 Commissioning tools - PC or IOP Handheld Kit SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 64: Wiring Example For The Factory Settings

    For a complete technical specification of the individual connections, as shown in the following diagram, please refer to following figures: ● Figure 3-8 SINAMICS G110M CU240M USS terminal diagram (Page 57) ● Figure 3-9 SINAMICS G110M CU240M PROFIBUS terminal diagram (Page 58) ●...
  • Page 65 Figure 4-2 Default wiring of the SINAMICS G110M CU240M USS Figure 4-3 Default wiring of the SINAMICS G110M CU240M DP and CU240M PN Note Unswitched and switched power supply The unswitched 24 V power supply (also known as non-switched) on X1.2 and X1.4 provides power to the general electronics of the Control Unit.
  • Page 66: Factory Setting Of The Inverter Control

    For a control command at the respective digital input, the motor rotates with ±150 rpm. The ramp-up and ramp-down times are also 10 seconds, referred to 1500 rpm. Figure 4-5 Jogging the motor in the factory setting SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 67: V/F Control Or Speed Control

    ● When the maximum motor speed exceeds the following values: Converter pulse frequency 2 kHz 4 kHz and higher Pole number of the motor 4-pole 4-pole Maximum motor speed [rpm] 4980 7200 SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 68: P0015 Macros

    Fieldbus communications with Command Dataset selection (default for CU240M DP and CU240M PN) Figure 4-7 Standard input and output with motorized potentiometer Figure 4-8 Standard input and output with analog setpoint Figure 4-9 Two-wire control SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 69 Figure 4-10 Three-wire control Figure 4-11 USS fieldbus communications Figure 4-12 Conveyor with two fixed speeds Figure 4-13 Conveyor with potentiometer and one fixed speed (default for the CU240M USS) SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 70: Basic Commissioning With Dip Switches

    DIP switches. The DIP switches are located on the communications board within the Control Unit housing, as shown in the figure below. Figure 4-14 DIP Switches location SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 71 If the DIP switch is activated for a specific function, then the parameters for that function cannot be modified by manually editing the parameter value, i.e. ready-only. SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 72 PROFIBUS address DIP-switch for use with the PROFIBUS and USS variant of the CU240M. Examples of the DIP switches and their individual settings are illustrated in the figures below. Figure 4-16 PROFIBUS address DIP Switch SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 73 Commissioning 4.6 Basic Commissioning with DIP switches Figure 4-17 Commissioning DIP Switch 1 SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 74 Commissioning 4.6 Basic Commissioning with DIP switches Figure 4-18 Commissioning DIP Switch 2 SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 75: Basic Commissioning With Iop

    Note Equipment required to commission system with the IOP To commission the SINAMICS G110M system using the Intelligent Operator Panel (IOP), the user will require the IOP Hand-held Kit (IOP HHK) and the special optical communications cable. The order details for these items are given below.
  • Page 76 The Motor Data screen indicates the frequency charac- teristic of the attached motor. Input the correct Motor Voltage from the motor rating plate. SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 77 Inverter. 13. Select the macro that is suitable for your application. Once selected all inputs, outputs, command sources and setpoints will be automatically configured by the soft- ware. SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 78 If save is selected, a factory reset will be performed then the settings are saved to the Inverter memory. The loca- tion of saved data is assigned using the "Parameter sav- ing mode" function in "Parameter settings" in "Menu". SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 79: Basic Commissioning With Starter

    Basic commissioning with STARTER STARTER and STARTER screen forms STARTER is a PC-based tool to commission Siemens inverters. The graphic user interface of STARTER supports you when commissioning your inverter. Most inverter functions are combined in screen forms in STARTER.
  • Page 80 6. Then click on "Update". The connected converters are now displayed in "Accessible nodes". 7. Close this screen form without selecting the converter(s) that has/have been found. 8. Create your STARTER project (Page 81). You have set the USB interface. SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 81: Generating A Starter Project

    "Search online for drive units ...". 3. Follow the instructions of the Wizard, and set everything that you require for your particular project. You have created your STARTER project. SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 82: Go Online And Start Wizard For Basic Commissioning

    ③ The converter is offline 4. When you are online, double-click on "Control Unit". 5. Start the wizard for basic commissioning. You are online and have started basic commissioning. SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 83 Exit basic commissioning. You have entered all of the data that is necessary for the basic commissioning of your inverter. SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 84: Identifying Motor Data

    • Before switching on, ensure that nobody is working on the machine or located within its working area. • Secure the machine's work area against unintended access. • Lower hanging/suspended loads to the floor. SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 85: Change Settings

    4.8.5 Change settings After the basic commissioning, you can adapt the inverter to your application as described in the Commissioning (Page 63). SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 86 You have saved your settings securely in the inverter in case of a power failure. Go offline You can now exit the online connection after the data backup (RAM to ROM) with "Disconnect from target system". SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 87: Optimize The Drive Using The Trace Function

    , you can define another trigger to start the measurement. Using pretrigger, set the time for the recording before the trigger is set. As a consequence, the trigger condition traces itself. SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 88 In the example, the trace starts if DI0 and DI3 are high and DI2 is low. The state of the other digital inputs is not relevant for the start of the trace. Further, you can either set an alarm or fault as start condition. SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 89 – or to separate zero lines. ● Measuring cursor on This allows you to analyze the measuring intervals in more detail. Figure 4-20 Trace dialog box SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 90 Commissioning 4.8 Basic commissioning with STARTER SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 91: Troubleshooting

    The location of the various LEDs on the Power Module and Communications and Power Interface (which is attached to the terminal housing) are shown in the figure below. Figure 5-1 Status LED locations SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 92 Table 5- 3 Description of PROFINET communications LED PROFINET LED Description of function LNK - On Link is active LNK - Off Link inactive with no data being transferred SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...
  • Page 93 SINAMICS G110M Getting Started Getting Started, 09/2014, FW V4.7, A5E31298643B AC...