Siemens SINAMICS G150 Operating Instructions Manual page 69

Converter cabinet units 75 kw to 1500 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Item
Activity
32
Option L87
Insulation
monitoring
Safety Integrated
33
Option K82
"Safe Torque
Off" and "Safe
Stop 1" safety
functions
Required tools
To install the connections, you will require:
● Spanner or socket spanner (w/f 10)
● Spanner or socket spanner (w/f 13)
● Spanner or socket spanner (w/f 16/17)
● Spanner or socket spanner (w/f 18/19)
● Hexagon-socket spanner (size 8)
● Torque wrench up to 50 Nm
● Screwdriver, size 2
● Screwdriver Torx T20
● Screwdriver Torx T30
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A
The insulation monitor can only be operated on an ungrounded
line supply (IT system). Only one insulation monitor can be used
in an electrically-connected network. For line-side control, the
signaling relays must be connected accordingly or, with individual
drives (the cabinet unit is fed via a converter transformer
assigned to the cabinet unit), integrated in the cabinet unit alarm
train (see "Electrical installation / Other connections / Insulation
monitoring (option L87)").
Point 9 must also be observed:
"Before the drive is operated on an ungrounded line supply (IT
system), the connection clip to the basic interference suppression
device must be removed" (see Chapter "Electrical
installation/Power connections/Removing the connection clip to
the interference suppression capacitor for operation on
ungrounded line supplies (IT systems)").
The terminal block -X41 must be connected line-side, the safety
functions must be activated prior to use via parameter
assignment, in addition an acceptance test must be performed
and an acceptance log must be created (see section "Electrical
installation / Other connections / Terminal module for activating
"Safe Torque Off" and "Safe Stop 1" (option K82)").
Electrical installation
4.2 Checklist for electrical installation
Yes
Completed
67