Siemens SINAMICS G150 Operating Instructions Manual page 376

Converter cabinet units 75 kw to 1500 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Setpoint channel and closed-loop control
7.2 Setpoint channel
Without ramp-function generator tracking
● p1145 = 0
● Drive accelerates to t2, although the setpoint after t1 is smaller than the actual value
With ramp-function generator tracking
● At p1145 > 1 (values between 0 and 1 are not applicable), ramp-function generator
● t1 and t2 are almost identical
Function diagram
FP 3060
FP 3070
FP 3080
Parameter
• r1119
• p1120
• p1121
• p1130
• p1131
• p1134
• p1135
• p1136
• p1137
• p1138
• p1139
• p1140
• p1141
• P1143
• P1144
• p1145
• P1148
• r1148
• r1150
• p1151
374
tracking is activated when the torque limit is approached. The ramp-function generator
output thereby only exceeds the actual speed value by the deviation value defined in
p1145.
Simple ramp-function generator
Extended ramp-function generator
Ramp-function generator selection, status word, tracking
CO: Ramp-function generator setpoint at the input
Ramp-function generator ramp-up time
Ramp-function generator ramp-down time
Ramp-function generator initial rounding time
Ramp-function generator final rounding time
Ramp-function generator rounding type
OFF3 ramp-down time
OFF3 initial rounding time
OFF3 final rounding time
CI: Up ramp scaling
CI: Down ramp scaling
BI: Enable ramp-function generator/disable ramp-function generator
BI: Continue ramp-function generator/freeze ramp-function generator
BI: Accept ramp-function generator setting value
CI: Ramp-function generator setting value
Ramp-function generator tracking intensity
Ramp function generator tolerance for ramp-up and ramp-down active
CO: Ramp-function generator acceleration
Ramp-function generator speed setpoint at the output
CO: Ramp-function generator configuration
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A