Commissioning
5.5 First commissioning with the AOP30
Settings for motor connection to a motor with one-winding system
Before the commissioning, a motor with several winding systems is automatically defined.
The setting for a one-winding system is made during commissioning by setting parameter
p7003 to 0.
Settings via the AOP30
During commissioning, you are asked whether a motor is connected to a one-winding
system or multiple winding system. This setting must be made according to the motor
connected.
NOTICE
If the "motor with a one-winding system" is not set using p7003 = 0, then the drive can be
powered down (tripped) during the motor identification routine with an "overcurrent" fault
message. The system will not be properly tuned.
NOTICE
When resetting (restoring) the parameterization to the factory setting, this setting must be
again made before the drive unit is re-commissioned.