● Pressing the "Update (F5)" button displays the IP address and name in the entry for the
● If the Ethernet interface is displayed as bus node, mark the entry and press the "Accept"
● The SINAMICS drive is displayed as drive object in the project navigator.
● You can now configure the drive unit (see Chapter "Configuring the drive unit").
Note
The IP address and device name are stored on the memory card of the Control Unit (non-
volatile)..
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A
Note
ST (Structured Text) conventions must be satisfied for the name assignment of IO
devices in Ethernet (SINAMICS components). The names must be unique within
Ethernet.
The characters "-" and "." are not permitted in the name of an IO device.
Figure 5-34
Edit Ethernet Node
bus node. If not, close the "Accessible nodes" screen and perform another search for
accessible nodes.
button.
5.3 Procedure for commissioning via STARTER
Commissioning