Example 2: Writing Parameters (Multi-Parameter Request) - Siemens SINAMICS G150 Operating Instructions Manual

Converter cabinet units 75 kw to 1500 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Table 6- 22
Parameter response
Response header
Parameter value
Information about the parameter response:
● Request reference mirrored:
● Response ID:
● Axis mirrored, number of parameters:
● Format:
● Number of values:
● 1. value ... 8th value
6.7.4.4

Example 2: Writing parameters (multi-parameter request)

Preconditions
1. The PROFIdrive controller has been commissioned and is fully operational.
2. PROFIdrive communication between the controller and the device is operational.
3. The controller can read and write data records in conformance with PROFIdrive DPV1.
4. Control type: Vector control (with extended setpoint channel)
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A
Parameter response
Request reference mirrored
= 25 hex
Axis mirrored = 02 hex
Format = 06 hex
1. value = 1355 dec
2. value = 0 dec
...
8. value = 0 dec
This response belongs to the request with request reference 25.
01 hex → Read request positive, values available starting from 1st value
The values correspond to the values from the request.
06 hex → Parameter values are in the unsigned16 format.
08 hex → 8 parameter values are available.
A fault is only entered in value 1 of the fault buffer for drive 2.
Special requirements for this example:
6.7 Communication according to PROFIdrive
Response ID = 01 hex
Number of parameters = 01 hex
Number of values = 08 hex
Operation
Offset
0 + 1
2 + 3
4 + 5
6
8
...
20
331