Parameter
Meaning
value
5
Precise frequency
drives (textiles)
6
Precise frequency
drives with flux
current control (FCC)
7
Parabolic
characteristic and
ECO
19
Independent voltage
setpoint
Function diagram
FP 6300
Parameter
• p1300
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A
Characteristic (see parameter value 0) that takes into account the specific
technological features of an application (e.g. textile applications).
The current limitation (Imax controller) only affects the output voltage and not the
output frequency.
The slip compensation and resonance damping are disabled.
Characteristic (see parameter value 1) that takes into account the specific
technological features of an application (e.g. textile applications).
The current limitation (Imax controller) only affects the output voltage and not the
output frequency.
The slip compensation and resonance damping are disabled.
Voltage losses in the stator resistance for static / dynamic loads are also
compensated (flux current control, FCC). This is particularly useful for small motors,
since they have a relatively high stator resistance.
Characteristic (see parameter value 1) and Eco mode at constant operating point.
At constant operating point, the efficiency is optimized by varying the voltage.
Active slip compensation is necessary here; the scaling must be set so that the
slip is fully compensated (p1335 = 100%).
The user can define the output voltage of the Power Module independently of the
frequency using BICO parameter p1330 via the interfaces (e.g., analog input AI0 of
the TM31 –> p1330 = r4055[0]).
V/f characteristic and voltage boost
Open-loop/closed-loop control operating mode
Setpoint channel and closed-loop control
Application / property
7.3 V/f control
377