Derating data

Permissible output current as a function of the ambient temperature
The cabinet devices and the associated system components are rated for an ambient
temperature of 40 °C and installation altitudes up to 2000 m above sea level. The output
current must be reduced if the cabinet devices are operated at ambient temperatures above
40 °C. Ambient temperatures above 50 °C are not permissible. The following tables specify
the permissible output current as a function of the ambient temperature for the different
degrees of protection .
Table 12- 2
Current derating factors as a function of the ambient temperature (inlet air temperature at the air inlet of the
cabinet unit) and installation altitude for cabinet units with degree of protection IP20/IP21/IP23/IP43
Installation altitude
above sea level in m
0 ... 2000
Table 12- 3
Current derating factors as a function of the hambient temperature (inlet air temperature at the air inlet of the
cabinet unit) and installation altitude for cabinet units with degree of protection IP54
Installation altitude
above sea level in m
0 ... 2000
Installation altitudes between 2000 m and 5000 m above sea level
If the SINAMICS G150 cabinet units are operated at an installation altitude >2000 m above
sea level, it must be taken into account that the air pressure and, consequently, the air
density decreases. The lower air density also reduces the cooling efficiency and the
insulation capacity of the air.
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A
Storage
5
1.5 mm at
to 9 Hz
5 m/s² at > 9 to 200 Hz
1M2 to EN 60721-3-1
40 m/s² at 22 ms
1M2 to EN 60721-3-1
italics
at an ambient temperature (air intake temperature) of
20 °C
25 °C
100 %
100 %
at an ambient temperature (air intake temperature) of
20 °C
25 °C
100 %
100 %
Transport
3.1 mm
5
at
... 9 Hz
10 m/s² at > 9 ... 200 Hz
2M2 to EN 60721-3-2
100 m/s² at 11 ms
2M2 to EN 60721-3-2
.
Current derating factor
30 °C
35 °C
100 %
100 %
Current derating factor
30 °C
35 °C
100 %
100 %
Technical specifications
12.2 General data
Operation
0.075 mm at 10 ... 58 Hz
10 m/s² at >58 ... 200 Hz
-
100 m/s² at 11 ms
3M4 to EN 60721-3-3
40 °C
45 °C
100 %
93.3 %
40 °C
45 °C
93.3 %
86.7 %
50 °C
86.7 %
50 °C
80.0 %