Messages After Replacing Drive-Cliq Components - Siemens SINAMICS G150 Operating Instructions Manual

Converter cabinet units 75 kw to 1500 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

11.6

Messages after replacing DRIVE-CLiQ components

After DRIVE-CLiQ components are replaced (Control Interface Module, TM31, SMCxx) when
service is required, generally no message is output after power-up, since an identical
component is identified and accepted as component when the system boots.
The reason for this is that an identical component is detected and accepted as spare part
when running-up. If, unexpectedly, a fault message of the "topology fault" category is
displayed, then when replacing a component, one of the following faults/errors should have
occurred:
● A Control Interface Module with different firmware data was installed.
● When connecting-up DRIVE-CLiQ cables, connections were interchanged.
Automatic firmware update
As of firmware 2.5, an automatic firmware update can be carried out once the electronics
have been powered up on replacement DRIVE-CLiQ components.
● The following LEDs will flash slowly to indicate that an automatic firmware update is in
● Once the automatic firmware update is complete, the "RDY" LED on the Control Unit will
● To complete the automatic firmware update process, a POWER ON is required (switch
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A
progress: the "RDY" LED on the Control Unit (orange, 0.5 Hz) and an LED on the
relevant DRIVE-CLiQ component (green/red, 0.5 Hz).
CAUTION
The drive converter must not be shut down during this process!
flash quickly (orange, 2 Hz) along with an LED on the relevant DRIVE-CLiQ component
(green/red, 2 Hz).
the device off and back on again).
11.6 Messages after replacing DRIVE-CLiQ components
Maintenance and servicing
575