Siemens SINAMICS G150 Operating Instructions Manual page 191

Converter cabinet units 75 kw to 1500 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Note
In the circuit example, the power for the digital inputs (terminals -X122 and -X132) is
supplied from the internal 24 V supply of the Control Unit (terminal -X124).
The two groups of digital inputs (optocoupler inputs) each have a common reference
potential (ground reference M1 or M2). To close the circuit when the internal 24 V supply is
used, the ground references M1/M2 are connected to internal ground M.
If power is not supplied from the internal 24 V supply (terminal -X124), the jumper between
grounds M1 and M or M2 and M must be removed in order to avoid potential rounding. The
external ground must then be connected to terminals M1 and M2.
The rapid inputs can be used as probe inputs or as inputs for the external zero mark.
X100 to X103: DRIVE-CLiQ interface
Table 4- 74
DRIVE-CLiQ interface X100 – X103
Pin
1
2
3
4
5
6
7
8
A
B
Connector type: RJ45 socket
Blanking plate for DRIVE-CLiQ interfaces (50 pcs.) Order number: 6SL3066-4CA00-0AA0
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A
Signal name
TXP
TXN
RXP
Reserved, do not use
Reserved, do not use
RXN
Reserved, do not use
Reserved, do not use
+ (24 V)
M (0 V)
Electrical installation
4.11 Other connections
Technical data
Transmit data +
Transmit data -
Receive data +
Receive data -
Power supply
Electronics ground
189