Restrictions
● Pulse frequency wobbling can only be activated under the following conditions
● p1811 (Pulse frequency wobbling amplitude) can only be set under the following
● When pulse frequency wobbling is activated and impulses are enabled, the maximum
● When pulse frequency wobbling is activated and impulses are enabled, if the maximum
● When pulse frequency wobbling is activated and impulses are suppressed, if the
Note
If pulse frequency wobbling is deactivated (p1810.2 = 0), then all the indices of parameter
p1811 are set to 0.
Parameters
• p1800
• p1810.2
• p1811[D] Pulse frequency wobbling amplitude
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A
(p1810.2 = 1):
– The drive is pulse suppressed.
– p1800 < 2 x 1000 / p0115[0]
conditions:
– p1802.2 = 1
– p0230 (output filter) < 3 (no sine-wave filter)
pulse frequency (p1800) can be set as follows:
– For p1811 = 0: p1800 ≤ 2 x 1000 / p0115[0]
– For p1811 > 0: p1800 ≤ 1000 / p0115[0]
pulse frequency (p1800) is set to be greater than 1000 / p0115[0], then p1811 is set to 0.
maximum pulse frequency (p1800) is set to be greater than 2 x 1000 / p0115[0], then
p1811 and p1810.2 are set to 0.
Pulse frequency setpoint
Wobbling activated
Functions, Monitoring, and Protective Functions
9.2 Drive Functions
457