Siemens SINAMICS G150 Operating Instructions Manual page 328

Converter cabinet units 75 kw to 1500 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Operation
6.7 Communication according to PROFIdrive
Error
value
0x06
Illegal set operation (only reset
allowed)
0x07
Description element cannot be
changed
0x09
No description data available
0x0B
No parameter change rights.
0x0F
No text array exists
0x11
Request cannot be executed due to
operating status.
0x14
Illegal value.
0x15
Response too long.
0x16
Illegal parameter address.
0x17
Illegal format.
0x18
Number of values inconsistent.
0x19
Drive object does not exist.
0x65
Parameter presently deactivated.
0x6B
Parameter %s [%s]: no write access
for the enabled controller.
0x6C
Parameter %s [%s]: unit unknown.
0x6D
Parameter %s [%s]: write access only
in the commissioning state, encoder
(p0010 = 4).
0x6E
Parameter %s [%s]: write access only
in the commissioning state, motor
(p0010 = 3).
0x6F
Parameter %s [%s]: write access only
in the commissioning state, power
module (p0010 = 2).
0x70
Parameter %s [%s]: write access only
in quick commissioning (p0010 = 1).
0x71
Parameter %s [%s]: write access only
in the ready state (p0010 = 0).
326
Meaning
Comment
Modification access with a value not equal to 0 in a case
where this is not allowed.
Modification access to a description element that cannot
be changed.
Access to a description that does not exist (the parameter
value exists).
Modification access with no parameter change rights.
Access to a text array that does not exist (the parameter
value exists).
Access is temporarily not possible for unspecified reasons. –
Modification access with a value that is within the limits but
is illegal for other permanent reasons (parameter with
defined individual values).
The length of the present response exceeds the maximum
transfer length.
Illegal or unsupported value for attribute, number of
elements, parameter number, subindex or a combination
of these.
Write request: illegal or unsupported parameter data
format.
Write request: a mismatch exists between the number of
values in the parameter data and the number of elements
in the parameter address.
You have attempted to access a drive object that does not
exist.
You have tried to access a parameter that, although
available, does not currently perform a function
(e.g., n control set and access to a U/f control parameter).
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A
Additional
info
Subindex
Subindex
Subindex