Selecting options
Figure 5-14
⇒ From the combination box Options selection: select the options belonging to your drive
unit by clicking on the corresponding check box (see type plate).
CAUTION
If a sine-wave filter (option L15) is connected, it must be activated when the options are
selected to prevent the filter from being destroyed.
NOTICE
During option selection it is essential to activate any motor reactor (option L08) or du/dt
filter (option L07, L10) being used, otherwise the motor control will not perform at its best.
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A
Selecting options
5.3 Procedure for commissioning via STARTER
Commissioning
213