Status after commissioning

LOCAL mode (control via operator panel)
● You switch to LOCAL mode by pressing the "LOCAL/REMOTE" key.
● Control (ON/OFF) is carried out via the "ON" and "OFF" keys.
● You can specify the setpoint using the "increase" and "decrease" keys or by entering the
Analog outputs (with option G60 "Customer terminal module TM31")
● The actual speed (r0063) is output as a current output in the range 0 to 20 mA at analog
● The actual current value (r0068) is output as a current output in the range 0 to 20 mA at
Digital outputs (with option G60 "Customer terminal module TM31")
● The "enable pulses" signal is output at digital output 0 (X542:2 and 3).
● The "no fault active" signal is output at digital output 1 (X542:5 and 6) (protection against
● The "ready for power up" signal is output at digital output 8 (X541:2).
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A
appropriate numbers using the numeric keypad.
output 0 (X522:2 and 3).
A current of 20 mA is equal to the maximum speed in p1082.
analog output 1 (X522:5 and 6).
A current of 20 mA corresponds to the current limit (p0640), which is set to 1.5 times the
rated motor current (p0305).
wire break).
Commissioning
5.6 Status after commissioning