Commissioning
5.3 Procedure for commissioning via STARTER
Figure 5-5
⇒ Under Access point: select the interface corresponding to your device configuration from:
● Select the S7ONLINE access (STEP7), if the connection to the drive unit is established
● Select the DEVICE access, if the connection to the drive unit is established via the
⇒ Click PG/PC ... and set up the interface in accordance with your device configuration.
The Properties..., Copy... and Select... pushbuttons are now active.
206
Set up interface
via PROFINET or PROFIBUS.
Ethernet interface.
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A