7.2.2

Direction reversal

Description
Due to the direction reversal in the setpoint channel the drive can be operated in both
directions with the same setpoint polarity.
Use the p1110 or p1111 parameter to block negative or positive direction of rotation.
Note
If an incorrect rotating field was connected when the cables were installed, and the cabling
cannot be changed, the rotating field can be corrected during drive commissioning via p1821
(rotating field direction reversal) to allow a direction reversal (see section "Direction
reversal"). Modifying parameters p1821 produces a direction reversal of the motor and the
encoder actual value without changing the setpoint.
Prerequisites
Direction reversal is triggered:
● via PROFIBUS by means of control word 1, bit 11
● via the cabinet operator panel (LOCAL mode) with the "Direction reversal" key.
Note
Note that only one direction of rotation is enabled in the delivery condition when control is
carried out via the AOP30.
Function diagram
FP 3040
Parameter
• p1110
• p1111
• p1113
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A
Direction of rotation limiting and direction of rotation changeover
BI: Inhibit negative direction
BI: Inhibit positive direction
BI: Setpoint inversion
Setpoint channel and closed-loop control
7.2 Setpoint channel