Structure Of The Telegrams - Siemens SINAMICS G150 Operating Instructions Manual

Converter cabinet units 75 kw to 1500 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Telegram interconnections
After changing p0922 = 999 (factory setting) to p0922 ≠ 999, the telegrams are
interconnected and blocked automatically.
Note
Telegrams 20 and 352 are the exceptions. Here, the PZD06 in the send telegram and
PZD03 to PZD06 in the receive telegram can be interconnected as required.
When you change p0922 ≠ 999 to p0922 = 999, the previous telegram interconnection is
retained and can be changed.
Note
If p0922 = 999, a telegram can be selected in p2079. A telegram interconnection is
automatically made and blocked. However, the telegram can also be extended.
This is an easy method of creating extended telegram interconnections on the basis of
existing telegrams.
6.7.3.2

Structure of the telegrams

Table 6- 14
Structure of the telegrams
Telegr.
PZD 1
PZD 2
1
STW1
NSOLL_A
ZSW1
NIST_A
2
STW1
ZSW1
3
STW1
ZSW1
4
STW1
ZSW1
20
STW1
NSOLL_A
ZSW1
NIST_A_
GLATT
220
STW1_
BM
ZSW1_
NIST_A
BM
352
STW1
NSOLL_A
ZSW1
NIST_A_
GLATT
999
STW1
free
ZSW1
free
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A
PZD 3
PZD 4
NSOLL_B
STW2
NIST_B
ZSW2
NSOLL_B
STW2
NIST_B
ZSW2
NSOLL_B
STW2
NIST_B
ZSW2
IAIST_
MIST_
GLATT
GLATT
NSOLL_B
STW2_BM
IAIST
MIST
PCS7_3
PCS7_4
IAIST_
MIST_
GLATT
GLATT
free
free
free
free
6.7 Communication according to PROFIdrive
PZD 5
PZD 6
G1_STW
G1_ZSW
G1_XIST1
G1_STW
G2_STW
G1_ZSW
Further assignment, see FP2420
PIST_
MELD_
GLATT
NAMUR
M_ADD
M_LIM
WARN_
FAULT_
CODE
CODE
PCS7_5
PCS7_6
WARN_
FAULT_
CODE
CODE
free
free
free
free
PZD 7
PZD 8
PZD 9
G1_XACT2
free
free
free
ZSW2_
free
free
BM
free
free
free
free
free
free
Operation
PZD 10
free
free
free
free
319