Connection For External Auxiliary Equipment (Option L19) - Siemens SINAMICS G150 Operating Instructions Manual

Converter cabinet units 75 kw to 1500 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

4.11.6

Connection for External Auxiliary Equipment (Option L19)

Description
This option includes an outgoing circuit fused at max. 10 A for external auxiliary equipment
(e.g. separately-driven fan for motor). The voltage is tapped at the converter input upstream
of the main contactor/circuit-breaker and, therefore, has the same level as the supply
voltage. The outgoing circuit can be switched within the converter or externally.
Connecting
Table 4- 39
Terminal
1)
Max. connectable cross-section: 4 mm²
Note
The connection for external auxiliary equipment must be set in accordance with the
connected consumer (-Q155).
Circuit proposal for controlling the auxiliary contactor from within the converter
Circuit proposal as standard
A free digital output of the Control Unit can be used to control the auxiliary contactor; it uses
a line-side relay to control auxiliary contactor -K155.
Signal r0899.11 (pulses enabled) must also be interconnected to the selected digital output
of the Control Unit.
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A
Terminal block X155 - Connection for external auxiliary equipment
Designation
1
L1
2
L2
3
L3
11
Contactor control
12
13
NO: Checkback
motor circuit breaker
14
15
NO: Checkback from
contactor
16
PE
PE
NO: NO contact
1)
Electrical installation
4.11 Other connections
Technical data
3 AC 380 ... 480 V
3 AC 500 ... 600 V
3 AC 660 ... 690 V
230 V AC
230 V AC / 0.5 A
24 V DC / 2 A
240 V AC / 6 A
PE
129