Functions, Monitoring, and Protective Functions
9.3 Extended functions
Description of load monitoring
This function monitors power transmission between the motor and the working machine.
Typical applications include V-belts, flat belts, or chains that loop around the belt pulleys or
cog wheels for drive and outgoing shafts and transfer the peripheral speeds and forces.
Load monitoring can be used here to identify blockages in the working machine and
interruptions to the power transmission.
During load monitoring, the current speed/torque curve is compared with the programmed
speed/torque curve (p2182 to p2190). If the current value is outside the programmed
tolerance bandwidth, a fault or alarm is triggered depending on parameter p2181. The fault
or alarm message can be delayed by means of parameter p2192 to prevent false alarms
caused by brief transitional states.
Figure 9-17
Commissioning
The "extended monitoring functions" function module can be activated by running the
commissioning wizard. Parameter r0108.17 indicates whether it has been activated.
494
Load monitoring (p2181 =1)
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A