Measurement With Up To 12 Channels - Siemens SINAMICS G150 Operating Instructions Manual

Converter cabinet units 75 kw to 1500 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Functions, Monitoring, and Protective Functions
9.4 Monitoring and protective functions
Temperature measurement with a sensor in 4-wire technology
With p4108[0...5] = 3, you sense the signals from a sensor in 4-wire technology at a 4-wire
connection at terminals 3(+) and 4(-).
The measuring cable is connected at terminal 1(+) and 2(-).
9.4.6.3

Measurement with up to 12 channels

Temperature measurement with two sensors in 2-wire technology
With p4108[0...5] = 1 you can acquire the signals from two sensors in 2-wire technology.
The first sensor is connected at terminal 1(+) and 2(-).
The second sensor (number = first sensor + 6) is connected at terminals 3(+) and 4(-).
When connecting two sensors in 2-wire technology to terminal X531, the first sensor is
assigned to temperature channel 1 and the second sensor is assigned to channel 7 (1+6).
NOTICE
Connection diagram for 12 temperature channels
The temperature sensors connected to a TM150 are not numbered consecutively. The first
6 temperature channels retain their numbering of 0 to 5. The other 6 temperature channels
are consecutively numbered from 6 to 11, starting at terminal X531.
Example of 8 temperature channels:
2x2 conductors at terminal X531: p4108[0] = 1 ≙ sensor 1 is at channel 0 and sensor 2 is at
channel 6
2x2 conductor at terminal X532: p4108[1] = 1 ≙ sensor 1 is at channel 1 and sensor 2 is at
channel 7
1x3 conductor at terminal X533: p4108[2] = 2 ≙ sensor 1 is at channel 2
1x3 conductor is at terminal X534: p4108[3] = 2 ≙ sensor 1 is at channel 3
1x4 conductor is at terminal X535: p4108[4] = 3 ≙ sensor 1 is at channel 4
1x2 conductor is at terminal X536: p4108[5] = 0 ≙ sensor 1 is at channel 5
508
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A