The converter is equipped with an overload reserve to deal with breakaway torques, for
example.
In drives with overload requirements, the appropriate base load current must, therefore, be
used as a basis for the required load.
The overloads apply under the precondition that the converter is operated at its base-load
current before and after the overload (a duty cycle duration of 300 s is used as a basis here).
Low overload
The base-load current for low overload (I
150% for 10 s.
Figure 12-2
High overload
The base-load current for a high overload I
160% for 10 s.
Figure 12-3
586
Low overload
High overload
) is based on a load duty cycle of 110% for 60 s or
L
is based on a duty cycle of 150% for 60 s or
H
Operating Instructions, 03/2012, A5E03263466A