Siemens SINAMICS G150 Operating Instructions Manual page 250

Converter cabinet units 75 kw to 1500 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Commissioning
5.5 First commissioning with the AOP30
NOTICE
A filter on the motor side must be entered in p0230:
• Option L07 – dV/dt filter compact plus Voltage Peak Limiter: p0230 = 2
• Option L08 – motor reactor: p0230 = 1
• Option L10 – dV/dt filter plus Voltage Peak Limiter: p0230 = 2
• Option L15 – sine-wave filter: p0230 = 3
Otherwise the motor control cannot function optimally.
When p0230 = 4 "External sine-wave filter", a separate sine-wave filter can be entered. An
input mask for specific filter data then appears.
Note
The choice "no selection" is also available as default setting for the command and setpoint
sources; if selected, no default settings are applied for the command and setpoint sources.
248
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A

Advertisement

Table of Contents
loading

Table of Contents