Insulation Test - Siemens SINAMICS G150 Operating Instructions Manual

Converter cabinet units 75 kw to 1500 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Electrical installation

4.3 Insulation test

4.3
Insulation test
Insulation test
In accordance with EN 60204-1, an insulation test must be performed on the
machine/system.
The test may be done with one of the following tests:
● Insulation resistance test
● Voltage test
Disconnect the machine/system from the line supply prior to testing.
Insulation resistance testing
Insulation resistance testing should be preferably carried out. The insulation resistance when
carrying out the test must not be less than 1 MΩ Testing is carried out with 500 V DC
between the main-circuit conductors
carried out on individual sections of the system.
Exception: A lower resistance value is permissible for certain components of the electrical
equipment; however, the value must not be lower than 50 kΩ.
SINAMICS cabinet units are covered by this exception. They must therefore be disconnected
during testing and tested separately.
1) Main circuits are circuits that are electrically connected to the line voltage.
Voltage test
Test equipment to EN 61180-2 should be used for voltage testing.
The rated frequency for the test voltage must be 50 Hz or 60 Hz.
The maximum test voltage must be either twice the rated voltage value for the equipment
power supply or 1000 V. The higher of the two values should be used. The maximum test
voltage must be applied between the conductors of the main circuits
conductor system for approx. 1 s.
Components and devices that are not rated to withstand this test voltage must be
disconnected prior to testing.
68
WARNING
WARNING
and the protective conductor system. Testing may be
1)
Operating Instructions, 03/2012, A5E03263466A
and the protective
1)
Converter cabinet units

Advertisement

Table of Contents
loading

Table of Contents