6.10 Communication via SINAMICS Link
11. Define the receive data for node 1
12. At the two nodes carry-out a "Copy RAM to ROM" to backup the parameterization and the
13. For both nodes, perform a POWER ON in order to activate the SINAMICS Link
Figure 6-46
SINAMICS Link: Configuration example
360
– Specify the data that should be placed in the receive buffer p8872 of node 1 in
location 0, received from node 2:
p8872[0] = 2
– Define that PZD1 of node 2 is saved in the receive buffer p8870 of node 1 in location
0:
p8870 [ 0] = 1
– r2050[0] now contains the value of PZD 1 of node 2.