Siemens SINAMICS G150 Operating Instructions Manual page 199

Converter cabinet units 75 kw to 1500 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Table 4- 84
Terminal block -X2 – connection NAMUR control terminal block
Terminal
Designation
10
11
12
13
14
15
16
17
18
30
31
32
33
34
35
36
50/51
AI 0/4-20 mA
60/61
AO 0/4-20 mA
62/63
AO 0/4-20 mA
Max. connectable cross-section: 2.5 mm²
Table 4- 85
Terminal block -X3 – connection for the motor PTC thermistor sensor
Terminal
Designation
90/91
Max. connectable cross-section: 2.5 mm²
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A
DI
ON/OFF (dynamic)/
DI
DI
DI
DI
DI
DI
Counterclockwise
DI
Power Disconnection
DO (COM)
Ready for operation
DO (NO)
DO (COM)
DO (NO)
DO (NO)
DO (COM)
DO (NC)
AI
Connection for a PTC
Default
ON/OFF (static)
OFF (dynamic)
Faster
Slower
RESET
Interlock
Motor turning
Fault
Speed setpoint
Motor frequency
Motor current
Default
thermistor
Electrical installation
4.11 Other connections
Comment
Effective operation can be coded by a wire
jumper on terminal -X400:9;10 (delivery
condition: jumper inserted):
jumper inserted: ON/OFF (dynamic)/
jumper removed: ON/OFF (static)
Motorized potentiometer
Motorized potentiometer
Acknowledge error
OFF2
"0" signal: CW phase sequence
"1" signal: CCW phase sequence
EMERGENCY OFF circuit
"0" signal: Power disconnection
"1" signal: No power disconnection
Relay output (NO contact)
Relay output (NO contact)
Relay output (two-way contact)
Default: 4 ... 20 mA
Default: 4 ... 20 mA
(Preassigned the motor frequency, can be
reparameterized for other variables)
Default: 4 ... 20 mA
(Preassigned the motor current, can be
reparameterized for other variables)
Comment
Shutdown if limit value is exceeded.
197