Thermistor Motor Protection Unit (Option L83/L84) - Siemens SINAMICS G150 Operating Instructions Manual

Converter cabinet units 75 kw to 1500 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Electrical installation
4.11 Other connections
4.11.16

Thermistor Motor Protection Unit (Option L83/L84)

Description
This option includes the thermistor motor protection unit (with PTB approval) for PTC
thermistor sensors (PTC resistor type A) for warning and shutdown. The power supply for
the thermistor motor protection unit is provided inside the converter where the evaluation is
also performed.
Option L83 triggers the "external alarm 1" (A7850) if a fault occurs.
Option L84 triggers the "external fault 1" (F7860) if a fault occurs.
Connection
Table 4- 55
The PTC thermistor sensors are connected directly to terminals T1 and T2 of the evaluation
unit.
Table 4- 56
Diagnostics
Messages output during operation and in the event of faults (meaning of LEDs on -B125,
B127) are described in the Operating Instructions in the customer DVD supplied with the
equipment.
150
-B127/B125 – connection for thermistor motor protection device
Equipment designation
-B127: T1, T2
-B125: T1, T2
Maximum cable length for the sensor circuit
Line cross-section in mm²
2.5
1.5
0.5
Description of function
Thermistor motor protection (alarm)
Thermistor motor protection (shutdown)
Line length in m
2 x 2800
2 x 1500
2 x 500
Operating Instructions, 03/2012, A5E03263466A
Converter cabinet units

Advertisement

Table of Contents
loading

Table of Contents