Namur Terminal Block (Option B00) - Siemens SINAMICS G150 Operating Instructions Manual

Converter cabinet units 75 kw to 1500 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Electrical installation
4.11 Other connections
4.11.31

NAMUR terminal block (option B00)

Description
The terminal block is designed in accordance with the requirements and guidelines defined
by the standards association for measurement and control systems in the chemical industry
(NAMUR – recommendation NE37), that is, certain device functions are assigned to fixed
terminals. The inputs and outputs assigned to the terminals fulfill PELV ("protective extra-low
voltage and protective separation") requirements.
The terminal block only contains the necessary functions. Unlike the NAMUR
recommendation, optional terminals are not available.
The 24 V DC is supplied on the line side via terminals -X2:1-3 (protected with 1 A within the
converter). You must ensure that the PELV safety requirements (protective extra-low voltage
with protective separation) are fulfilled.
To monitor the temperature of explosion-proof motors, option B00 features a PTC thermistor
release mechanism with PTB approval. Shutdown if limit value is exceeded. The associated
PTC sensor is connected to terminal -X3:90, 91.
The terminal block is divided into three sections:
● -X1; -X2: for the power connections
● -X2: for signal cables, which must fulfill PELV requirements with electrical separation.
● -X3: for connecting the motor PTC thermistor detector
Connecting
Table 4- 83
Terminal block -X2 - connection 24 V supply
Terminal
Designation
1
2
3
Max. connectable cross-section: 2.5 mm²
196
M
Reference conductor
P24 V
24 V DC supply
P24 V
24 V DC outgoing circuit
Default
Comment
Protected internally with fuse (1 A)
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A

Advertisement

Table of Contents
loading

Table of Contents