Siemens SINAMICS G150 Operating Instructions Manual page 412

Converter cabinet units 75 kw to 1500 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Setpoint channel and closed-loop control
7.4 Vector speed/torque control with/without encoder
Supplementary conditions
● Maximum speed or maximum torque depend on the converter output voltage available
● Calculating the maximum speed:
● Depending on the terminal voltage and load cycle, the maximum torque can be taken
● No thermal model is available for the closed-loop control of a permanent-magnet
Commissioning
The following sequence is recommended for commissioning:
● Configure the drive
● Motor identification (standstill measurement, p1910)
● Speed controller optimization (rotary measurement, p1960)
Motor data for permanent-magnet synchronous motors
Table 7- 2
Motor data type plate
Parameter
Description
p0304
Rated motor voltage
p0305
Rated motor current
p0307
Rated motor power
p0310
Rated motor frequency
p0311
Rated motor speed
p0314
Motor pole pair number
p0316
Motor torque constant
410
and the back EMF of the motor (calculation specifications: EMF must not exceed U
).
converter
from the motor data sheets / configuration instructions.
synchronous motor. The motor can only be protected against overheating by using
temperature sensors (PTC, KTY). To achieve a high level of torque accuracy, we
recommend the use of a temperature sensor (KTY) to measure the motor temperature.
When the drive is being commissioned using STARTER or the AOP30 operator panel,
the permanent-magnet synchronous motor must be selected. The motor data specified in
the table below must then be entered. Finally, the motor identification routine and speed
optimization (p1900) are activated. Encoder adjustment is activated automatically
together with the motor identification routine.
Comment
If this value is not known, the value "0" can also be
entered.
Entering the correct value, however, means that the
stator leakage inductance (p0356, p0357) can be
calculated more accurately.
If this value is not known, the value "0" can also be
entered.
If this value is not known, the value "0" can also be
entered.