Temperature Measurement Via Tm150 (Option G51); Description - Siemens SINAMICS G150 Operating Instructions Manual

Converter cabinet units 75 kw to 1500 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Functions, Monitoring, and Protective Functions
9.4 Monitoring and protective functions
9.4.6

Temperature measurement via TM150 (option G51)

9.4.6.1

Description

The Terminal Module 150 (TM150) has 6x 4-pole terminals for temperature sensors.
Temperature sensors can be connected in a 1x2, 1x3 or 1x4-wire system. In a 2x2-wire
system, up to 12 input channels can be evaluated. 12 input channels can be evaluated in the
factory setting. The temperature channels can be combined into 3 groups and evaluated
together.
PTC, KTY84, bimetallic NC contact, PT100 and PT1000 temperature sensors can be
connected and evaluated. The fault and/or alarm thresholds of the temperature values can
be set from -99 °C up to 251°C.
The temperature sensors are connected at terminal strips X531 to X536 according to the
following table.
The TM150 temperature inputs are not electrically isolated.
Selecting the sensor types
● p4100[0...11] sets the sensor type for the respective temperature channel.
● r4105[0...11] indicates the actual value of the temperature channel.
NOTICE
For PTC and bimetallic NC contact the following applies:
What is shown in r4105[0...11] does not correspond to the actual temperature value.
Table 9- 13
Value of p4100[0...11]
506
– For switching temperature sensors, such as e.g. PTC and bimetallic NC contact,
symbolically two limit values are displayed:
- r4105[0...11] = -50 °C: The temperature actual value is below the rated response
temperature.
- r4105[0...11] = +250 °C: The temperature actual value is above the rated response
temperature.
Selecting the sensor types
Temperature sensor
0
Evaluation disabled
1
PTC thermistor
2
KTY84
4
Bimetallic NC contact
5
PT100
6
PT1000
Temperature display range r4105[0...11]
-
-50 °C or +250 °C
-99 °C to +250 °C
-50 °C or +250 °C
-99 °C to +250 °C
-99 °C to +250 °C
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A

Advertisement

Table of Contents
loading

Table of Contents