in an RSC-S (PCM-30) Model B RCO2
Replacing a/an NT7X05 in RSC-S RCO2
At your current location
1
Proceed only if you were either directed to this card replacement procedure
from a step in a maintenance procedure, are using the procedure to verify or
accept cards, or were directed to this procedure by your maintenance support
group.
2
Obtain a replacement card. Ensure the replacement card has the same
product equipment code (PEC) including suffix, as the card to be removed.
At the MAP display
3
Access the PM level and post the RCO2 by typing
>MAPCI;MTC;PM;POST RCO2 rco2_no
and pressing the Enter key.
where
rc2_no
is the number of the RCO2 to be busied
Example of a MAP display:
DMS-100 Family NA100 Card Replacement Procedures Volume 6 of 7 LET0015 and up
XPM card replacement procedures (continued)
CAUTION
Loss of service
When replacing a card in the RCO2 ensure the unit where
you are replacing the card is INACTIVE and the mate unit is
ACTIVE.
1-227
NT7X05
(continued)