Nortel DMS-100 Series Replacement Procedures page 983

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

To replace an NTMX72 in an RSC-M
At the MAP display
1
Proceed if one of the following conditions apply:
a step in a maintenance procedure directed you to this card replacement
procedure
you use this procedure to verify or accept cards
the maintenance support group directed you to this procedure.
2
Obtain an NTMX72 replacement circuit card. Make sure the replacement
circuit card has the same product engineering code (PEC) and PEC suffix, as
the circuit card to be removed.
At the MAP terminal
3
To access the peripheral module (PM) level of the MAP display and to post
the RSC-M/RCO2 with the defective card, type:
>MAPCI;MTC;PM;POST RCO2 rco2_no
and press the Enter key.
where
rco2_no
is the PM number zero to 255
Example of a MAP response:
DMS-100 Family NA100 Card Replacement Procedures Volume 6 of 7 LET0015 and up
XPM card replacement procedures (continued)
WARNING
Loss of service
When you replace a card in the RSC-M, make sure the unit in
which you replace the card is inactive and the mate unit is
active.
NTMX72
in an RSC-M
(continued)
1-951