1-184 XPM card replacement procedures (continued)
NT6X99
in an RSC-S (DS-1) Model B LCME
7
8
9
10
11
297-8021-547 Standard 14.02 May 2001
f
Ensure a card shroud and line card extractor are available.
Remove the line card to be replaced by following these substeps:
a
Slide a card shroud over the card to be removed and an adjacent card. If
there is not an adjacent card on either side, do not use the card shroud.
b
Grasp the edge of the card with a line card extractor at a point midway
between the top and bottom edges. Hold the extractor in your right hand.
c
Squeeze the handles of the extractor together to grasp the card tightly.
d
Hold the front cover of the line drawer to steady it using your left hand.
e
Pull the extractor away from the drawer, and the card will become
unplugged from its socket on the drawer backplane.
f
Continue pulling the card with the extractor until the card is clear of the
shroud.
g
Insert the card removed into the ESD container and store using local
procedures.
Replace the faulty card by following these substeps:
a
Remove the replacement card from the ESD container.
b
Slide the card in the shroud guide slots toward the drawer backplane.
c
Hold the front cover of the line drawer with your left hand to steady it.
d
Grasp the top and bottom edges of the card with the fingers of your right
hand.
e
Push the card toward the backplane until it plugs fully into the backplane
socket.
Continue this procedure depending on where you were when you were
directed to this procedure.
If you entered this procedure
from
alarm clearing procedures
other
Test the line card just replaced by typing
>DIAG
and pressing the Enter key.
If DIAG
passes
fails
Return the line card to service by typing
>RTS
(continued)
Do
step 14
step 10
Do
step 11
step 15