1-442 XPM card replacement procedures (continued)
NTBX01
in an SMU
(end)
15
16
17
18
19
20
297-8021-547 Standard 14.02 May 2001
If RTS
failed
Send any faulty cards for repair according to local procedure.
Record the following items in the office records:
date the card was replaced
serial number of the card
symptoms that prompted replacement of the card
Go to step 19.
Return to Alarm Clearing Procedures .
If necessary, go to the point where a faulty card list is initiated and identify the
next faulty card on the list. Go to the appropriate card replacement procedure
for that card.
Obtain further assistance in replacing this card by contacting the personnel
responsible for a higher level of support.
You have successfully completed this procedure. Remove the sign from the
active unit, return to the maintenance procedure that directed you to this card
replacement procedure, and continue as directed.
For further assistance with switch of activity, contact the personnel
responsible for the next level of support.
Note: If the system recommends using the SWACT command with the
FORCE option, consult office personnel to determine if use of the FORCE
option is advisable.
Do
step 18