1-46 XPM card replacement procedures (continued)
NT6X86
in an SMS-R
(continued)
15
16
17
18
At the frame
19
20
21
297-8021-547 Standard 14.02 May 2001
If you entered this procedure
from
other
Test the inactive unit by typing
>TST UNIT unit_no
and pressing the Enter key.
where
unit_no
is the number of the faulty SMS-R unit
If TST
passes
fails
Return the inactive SMS-R unit to service by typing
>RTS UNIT unit_no
and pressing the Enter key.
where
unit_no
is the number of the faulty SMS-R unit
If RTS
passes
fails
Return to Alarm Clearing Procedures section of this manual or to the
procedure that directed you to this procedure. At the point where a faulty card
list was produced, identify the next faulty card on the list and go to the
appropriate card replacement procedure for that card in this manual.
Obtain further assistance in replacing this card by contacting personnel
responsible for a higher level of support.
Remove the sign from the active SMS-R unit.
Send any faulty cards for repair according to local procedure.
Note the following in office records according to local policy:
the date the card was replaced
the serial number of the card
the symptoms that prompted replacement of the card
Do
step 15
Do
step 16
step 17
Do
step 19
step 18